        Vacuum interrupter for load breaking switch TF314C

        Model:VITF12/630-20

        Category:VI for load breaking switches


        Product details

        1435821951122937.jpg
        Main Technical Specification
        VOLTAGE RATINGS
        Rated voltage(Ur)kV12
        Rated short-time(1min)power-frequency withstand voltage(Ud)kV42
        Rated lightning impulse withstand voltage(Peak)(Up)kV85
        Rated frequency(fr)Hz50
        CURRENT RATINGS
        Rated current(Ir)A630
        Circuit resistance at lowest rated contact forceμΩ45
        Rated short-time withstand current(lk)kA20
        Rated duration of short-circuit(tk)s4
        Rated peak withstand current(lp)kA50
        Rated short-circuit making current(IMc)kA50
        Rated active load breaking current(l1)A630
        Rated closed-loop breaking current(l2a)A630
        Rated cable-charging breaking current(l4a)A10
        Rated breaking current of single capacitor bank(lsb)A400
        Rated breaking current of back-to-back capacitor bank(Ibb)A400
        MECHANICAL DATA
        Weight of movable partskg≤0.7
        Closing force due to bellow and atmosphereN80±30
        Force required to hold contacts open at full strokeN140±40
        MECHANICAL REQUIREMENTS
        Clearance between open contactsmm9±1
        Average opening speed (contact close position~75%contact gap)m/s1.0±0.2
        Average closing speed (30%contact gap-contact close position)m/s0.6±0.2
        Rated added external contact final forceN900±50
        Contact bouncing duration at closing operationms≤2
        Closing and opening non-simultaneity of three-phase contactsms≤2
        Maximum rebound during openingmm≤1.5
        LIFE
        Storage lifeyears20
        Rated mechanical enduranceTimes10000
        Contacts limit erosionmm3

        Relevant information